We need your consent to use the individual data so that you can see information about your interests, among other things. Click "OK" to give your consent.
Standard Test Method for Measurement of Hydrogen Sulfide in the Vapor Phase Above Residual Fuel Oils
STANDARD published on 1.6.2014
Designation standards: ASTM D5705-14
Note: WITHDRAWN
Publication date standards: 1.6.2014
SKU: NS-32221
The number of pages: 5
Approximate weight : 15 g (0.03 lbs)
Country: American technical standard
Category: Technical standards ASTM
Keywords:
hydrogen sulfide, length-of-stain detector tube, residual fuel oil, ICS Number Code 75.160.20 (Liquid fuels)
Significance and Use | ||||||||
5.1 Residual fuel oils can contain H5.1.1 The measurement of H5.2 This test method was developed to provide refineries, fuel terminals and independent testing laboratories, which do not have access to analytical instruments such as a gas chromatograph, with a simple and consistent field test method for the rapid determination of H2S in the vapor phase above residual fuel oils. Note 1: D5705 is one of
three test methods for quantitatively measuring H2S in residual fuels:
1) Test Method D6021 is an analytical test method to determine H2S levels in the liquid phase. 2) Test Method D7621 is a rapid test method to determine H2S levels in the liquid phase. Note 2: Because of the reactivity, absorptivity and volatility
of H5.3 This test method does not necessarily
simulate the vapor phase H2S concentration in a fuel
storage tank. It does, however, provide a level of consistency so
that the test result is only a function of the residual fuel oil
sample and not the test method, operator, or location. No general
correlation can be established between this field test and actual
vapor phase concentrations of H2S in residual fuel oil storage
or transports. However, a facility that produces fuel oil from the
same crude source under essentially constant conditions might be
able to develop a correlation for its individual case.
|
||||||||
1. Scope | ||||||||
1.1 This test method covers the field determination of hydrogen sulfide (H2S) in the vapor phase (equilibrium headspace) of a residual fuel oil sample. 1.2 The test method is applicable to liquids with a viscosity range of 5.5 mm2/s at 40°C to 50 mm2 /s at 100°C. The test method is applicable to fuels conforming to Specification D396 Grade Nos. 4, 5 (Heavy), and 6. 1.3 The applicable range is from 5 to 4000 parts per million by volume (ppm v/v) (micro mole/mole). 1.4 The values stated in SI units are to be regarded as standard. No other units of measurement are included in this standard. 1.5 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use. |
||||||||
2. Referenced Documents | ||||||||
|
Do you want to make sure you use only the valid technical standards?
We can offer you a solution which will provide you a monthly overview concerning the updating of standards which you use.
Would you like to know more? Look at this page.
Latest update: 2024-12-23 (Number of items: 2 217 157)
© Copyright 2024 NORMSERVIS s.r.o.