Standard Test Method for Fire Test of Non-Mechanical Fire Dampers Used in Vented Construction
Translate name
STANDARD published on 1.8.2017
Designation standards: ASTM E2912-17
Publication date standards: 1.8.2017
SKU: NS-796307
The number of pages: 19
Approximate weight : 57 g (0.13 lbs)
Country: American technical standard
Category: Technical standards ASTM
Keywords:
closed state, damper, fire, fire-test-response characteristic, gap, insulation, integrity, non-mechanical fire damper, open state, open state fire performance, opening, splice, vent, vented construction, void,, ICS Number Code 13.220.99 (Other standards related to fire protection)
Significance and Use | ||||||||||||||||||||||||
5.1 This test method provides for the following observations, measurements and evaluations of an open state during the test fire. 5.1.1 Ability of the test specimen to resist the passage of flames, radiation, and hot gases caused by sudden direct flame impingement. 5.1.2 Transmission of heat through the test specimen. 5.2 This test method does not provide the following: 5.2.1 Evaluation of the degree to which the test assembly contributes to the fire hazard by generation of smoke, toxic gases, or other products of combustion. 5.2.2 Measurement of the degree of control or limitation of the passage of smoke or products of combustion through the test specimen or the test assembly. 5.2.3 Measurement of flame spread over the surface of the test specimen or the test assembly. 5.2.4 Durability of the test specimen or test assembly under actual service conditions, including the effects of cycled temperature. 5.2.5 Effects of a load on the test specimen or test assembly. 5.2.6 Any other attributes of the test specimen or the test assembly, such as wear resistance, chemical resistance, air infiltration, water-tightness, and so forth. 5.3 The results of this test method shall not be used as an alternative to, or a substitute for, requirements for a required fire resistance rating of building construction. |
||||||||||||||||||||||||
1. Scope | ||||||||||||||||||||||||
1.1 This fire-test-response standard assesses the ability of non-mechanical fire dampers used in vented construction in its open state to limit passage of hot gases, radiation, and flames during a prescribed fire test exposure. The fire exposure condition in this test method is sudden direct flame impingement, which produces these hot gases, radiation, and flames. Note 1: Non-mechanical fire dampers can be used in vented
construction. Vented constructions may be parts of buildings
including walls, floors, ceilings and concealed spaces and cavities
used for air transfer and to allow ventilation in structures
without ductwork. Non-mechanical fire dampers can be located
adjacent to combustible construction or materials and situated in
exposed or concealed locations, or both. Unlike typical fire
resistive assemblies, vented construction uses non-mechanical fire
dampers to allow air transfer without the use of ducts. Resistance
to flame, radiation, and hot gases may be requirements when direct
flame impingement is a credible risk, or when no penetration of
flames is required by the authority having jurisdiction, or both.
The proposed test method provides procedures that enable an
assessment of this direct flame impingement on non-mechanical fire
dampers. This test method does not alter any requirements for
non-mechanical fire dampers used in fire resistance rated
construction and assemblies.
1.2 This fire-test-response standard is intended to provide a means to assess the reaction of a non-mechanical fire damper used in vented construction to sudden direct flame impingement, or as a supplement to existing fire-resistive test methods, or both. 1.3 This test method does not circumvent or eliminate the fire resistance rating requirements for construction. The fire resistance rating of construction shall be tested in accordance with published fire-resistance test standards as appropriate for the relevant application of the construction, or as required by the authority having jurisdiction (regulatory authority), or both. Non-mechanical fire dampers shall be tested to the appropriate fire-resistive test standards required for their application in order to determine a fire resistance rating in those constructions. Note 2: Some of the major international standards development
organizations (SDO) include, but are not limited to, ASTM
International, CEN, ISO, UL, and ULC. Some examples of standards
employing standard time-temperature curves for fire exposure used
to determine a construction’s fire resistance rating include, but
are not limited to, the following: Test Methods E119, E814, E1966, E2307, UL 10B, UL 10C, UL 555, UL 555C
etc. The term “authority having jurisdiction” is defined in
Practice E2174.
1.4 This test method specifies the fire exposure conditions, fire test protocol, and criteria to evaluate an open state. Note 3: There are currently no published test methods
(nationally or internationally) that address the application of
sudden direct flame impingement on non-mechanical fire dampers used
in vented construction. In the European Union (EU), CEN (European
Committee for Standardization) has very recently started a work
item to address reaction to sudden direct flame impingement on
non-mechanical fire dampers. Also, in the EU, some countries have
used large scale tests with 5MW fire exposures to assess test
specimens’ reactions to sudden direct flame impingement as part of
the entire building construction. Standard time-temperature curves
used to control gas-fired furnaces do not ensure a sudden direct
flame impingement on the test specimen, which this test method is
designed to do. A post flashover condition, the spontaneous
combustion of materials, ignition of a highly combustible material
acting as the source of the fire (for example, stored cleaning
solutions or fuels) or the location of materials can create a fire
scenario resulting in a sudden direct flame impingement.
1.5 Results generated by this test method provide the following information: 1.5.1 the open state fire performance of vented construction, and 1.5.2 the non-mechanical fire damper’s fire-test-response characteristic when exposed to sudden direct flame impingement. 1.6 This test method does not provide quantitative information about the test assembly related to the leakage of smoke, or gases, or both. 1.7 This test method does not apply to a test assembly having other components than those tested. 1.8 This standard is used to measure and describe the response of materials, products, or assemblies to heat and flame under controlled conditions, but does not by itself incorporate all factors required for fire hazard or fire risk assessment of the materials, products, or assemblies under actual fire conditions. 1.9 The text of this standard references notes and footnotes which provide explanatory material. These notes and footnotes (excluding those in tables and figures) shall not be considered requirements of this standard. 1.10 The values stated in SI units are to be regarded as standard. No other units of measurement are included in this standard. 1.11 Fire testing is inherently hazardous. Adequate safeguards for personnel and property shall be employed in conducting these tests. 1.12 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety, health and environmental practices and determine the applicability of regulatory limitations prior to use. 1.13 This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee. |
||||||||||||||||||||||||
2. Referenced Documents | ||||||||||||||||||||||||
|