We need your consent to use the individual data so that you can see information about your interests, among other things. Click "OK" to give your consent.
Standard Test Method for Water Penetration of Exterior Windows, Skylights, Doors, and Curtain Walls by Uniform Static Air Pressure Difference
STANDARD published on 1.2.2009
Designation standards: ASTM E331-00(2009)
Note: WITHDRAWN
Publication date standards: 1.2.2009
SKU: NS-46453
The number of pages: 5
Approximate weight : 15 g (0.03 lbs)
Country: American technical standard
Category: Technical standards ASTM
Keywords:
curtain walls, doors, skylights, water penetration, windows, Air pressure testing--building constructions/materials, Curtain walls, Doors/door assemblies, Exterior doors, Exterior windows, Fire-resistant materials/testing, Skylights, Uniform static air pressure difference, Water penetration--exterior windows/curtain walls/doors, Windows/window assemblies, ICS Number Code 91.060.10 (Walls. Partitions. Facades), 91.060.50 (Doors and windows)
Significance and Use | ||
This test method is a standard procedure for determining the resistance to water penetration under uniform static air pressure differences. The air-pressure differences acting across a building envelope vary greatly. These factors should be fully considered prior to specifying the test pressure difference to be used. Note 1—In applying the results of tests by this test method, note that the performance of a wall or its components, or both, may be a function of proper installation and adjustment. In service, the performance will also depend on the rigidity of supporting construction and on the resistance of components to deterioration by various causes, vibration, thermal expansion and contraction, etc. It is difficult to simulate the identical complex wetting conditions that can be encountered in service, with large wind-blown water drops, increasing water drop impact pressures with increasing wind velocity, and lateral or upward moving air and water. Some designs are more sensitive than others to this upward moving water. Note 2—This test method does not identify unobservable liquid water which may penetrate into the test specimen. |
||
1. Scope | ||
1.1 This test method covers the determination of the resistance of exterior windows, curtain walls, skylights, and doors to water penetration when water is applied to the outdoor face and exposed edges simultaneously with a uniform static air pressure at the outdoor face higher than the pressure at the indoor face. 1.2 This test method is applicable to any curtain-wall area or to windows, skylights, or doors alone. 1.3 This test method addresses water penetration through a manufactured assembly. Water that penetrates the assembly, but does not result in a failure as defined herein, may have adverse effects on the performance of contained materials such as sealants and insulating or laminated glass. This test method does not address these issues. 1.4 The proper use of this test method requires a knowledge of the principles of pressure measurement. 1.5 The values stated in SI units are to be regarded as the standard. The values given in parentheses are mathematical conversions to inch-pound units that are provided for information only and are not considered standard. 1.6 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use. For specific hazard statements, see 7.1. |
||
2. Referenced Documents | ||
|
Historical
1.2.2008
Historical
1.1.2007
Historical
15.2.2009
Historical
1.4.2012
Historical
1.10.2013
Historical
1.10.2010
Do you want to be sure about the validity of used regulations?
We offer you a solution so that you could use valid and updated legislative regulations.
Would you like to get more information? Look at this page.
Latest update: 2024-11-22 (Number of items: 2 206 568)
© Copyright 2024 NORMSERVIS s.r.o.